Product Price Quantity Delete

    Motor, PLC&HMI

    Omron PLC CP-series CP1E CPU Units CP1E-E10DT-D

    Omron PLC


     
    Item CP1E-E@@SD@-@ CP1E-E@@D@-@ CP1E-N@@S@D@-@ CP1E-N@@D@-@ CP1E-NA@@D@-@
    Transmission distance 5 m max.
    Built-in RS-232C port   

     

     

     

     

    No built-in RS-232C port

    Interface: Conforms to EIA RS-232C.
    Communications method Half duplex
    synchronization Start-stop
    Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
    Transmission distance 15 m max.
     Supported protocol · Host Link· 1:N NT Link

     

    · No-protocol mode

    · Serial PLC Links (master, slave)

    · Modbus-RTU Easy Master

     Built-in RS-485 port   

     

     

     

     

     

    No built-in RS-485 port

    N30/40/60S1-type onlyInterface: Conforms to EIA RS-485. 2-wire sensors No isolation
    Communications method Half duplex
    synchronization Start-stop
    Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
    Transmission distance 50 m max.
     Supported protocol · Host Link· 1:N NT Link

     

    · No-protocol mode

    · Serial PLC Links (master, slave)

    · Modbus-RTU Easy Master

    Serial Option port   

     

     

     

     

     

    Option Board cannot be mounted.

    N30/40/60 and NA20-type only 1 port
     Mountable Option Boards · One RS-232C port: CP1W-CIF01· One RS-422A/485 port (not isolated): CP1W-CIF11

     

    · One RS-422A/485 port (isolated): CP1W-CIF12-V1

    · One Ethernet port: CP1W-CIF41

    Communications method Depends on Option Board.
    synchronization Depends on Option Board.
    Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
     Compatible protocols · Host Link· 1:N NT Link

     

    · No-protocol mode

    · Serial PLC Links (master, slave)

    · Modbus-RTU Easy Master

     Number of tasks 17· One cyclic execution task

     

    · One scheduled interrupt task (always interrupt task 1)

    · Six input interrupt tasks (interrupt tasks 2 to 7)

    · Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16)

    Maximum subroutine number 128
    Maximum jump number 128
    Scheduled interrupt tasks 1 interrupt task
     Clock  Clock function not included.

     

    The time of error occurrence displays 01-01-01 01:01:01 Sunday

    Included.Accuracy (monthly deviation):

     

    -4.5 min to -0.5 min at ambient temperature of 55oC,

    -2.0 min to +2.0 min at ambient temperature of 25oC,

    -2.5 min to +1.5 min at ambient temperature of 0oC

    Built-in EEPROM Ladder programs and parameters are automatically saved to built-in EEPROM A section of the Data Memory Area can be saved to the built-in EEPROM.
     Battery backup With CP1W-BAT01  Battery (Sold separately)   

     

    Battery cannot be mounted.

    CP1W-BAT01 can be used. Maximum battery service life: 5 years Backup TimeGuaranteed value (ambient temperature: Battery (Sold separately)Effective value (ambient temperature: 25oC): 43,000 hours (approx. 5 years)
    Input Bits 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99)
    Output Bits 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199)
    Serial PLC Link Words 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289)
    Work Area (W) 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99)
    Holding Area (H) 800 bits (50 words): H0.00 to H49.15 (H0 to H49)Bits in this area maintain their ON/OFF status when operating mode is changed.
    Auxiliary Area (A) Read-only: 7,168 bits (448 words) A0 to A447Read/write: 4,896 bits (306 words) in words A448 to A753
    Temporary Relay Area (TR) (TR Area) 16 bits: TR0 to TR15
    Timer Area (T) 256 timer numbers (T0 to T255 (separate from counters))
    Counter Area (C) 256 counter numbers (C0 to C255 (separate from timers))

    Verification